Dicitur num est ut anteponendi.
| Range | 0-14 pH |
| Entry impedance | 1013 ohms |
| Temperature compensation | Automatic or fix |
| Accuracy | +/- 0.1pH |
| Hysteresis | Programmable from 0.06 to 0.051pH |
| Contact | Two contacts/without potential |
| Alarm relay | Max. 250VAC/3A/500VA |
| Affichage | Afficheur numérique 8 digits |
| Display | LCD 8 digits display |
| Power | 220V 50hz/24VAC/115V on request |
| Electrical consumption | 5VA |
| Environment | -10°C up to +55°C |
| Enclosure | Wall mounting in ABS with door IP65 or Panel mounting in ABS with door IP54 |
| Connection | Cable gland for wall mounting version Terminal block for panel mounting version BNC for the electrode |